HXGN-12/HXGN-24/HXGN-40.5

HXGN-12/HXGN-24/HXGN-40.5

HXGN-12/HXGN-24/HXGN-40.5

HXGN series incoming unit for ring-network and distribution-room feeder access.

Ключевые характеристики

Номинальное напряжение

12kV / 24kV / 40.5kV

Функция

Incoming feeder

Protection

Relay protection ready

Применение

Utility / Industrial

Product Overview

Our company can produce products with voltage classes ranging from 1kV to 40.5kV and below. The product is a complete set of power distribution devices composed of a high-voltage circuit breaker, load switch, contactor, high-voltage fuse, isolation switch, ground switch, transformer and station transformer, as well as control, measurement, protection, regulation devices, internal connectors, auxiliary shell and support parts.

The cabinet structure is assembled by bending and welding steel plates, and the protection level is IP2X. The upper part of the cabinet is the busbar room, and the instrument room is located in front of the busbar room and is separated by steel plates. The middle part of the cabinet is a switch room, and an insulating partition is arranged between the switch and other components.

Enforce Standards

  • IEC 62271 High Voltage Switchgear and Control Equipment
  • GB/T 11022 Standard Common Technical Requirements for High Voltage Switchgear and Control Equipment

Normal Service Condition

  • Ambient air temperature: -15 degrees Celsius to +40 degrees Celsius.
  • Altitude: 1000 meters and below.
  • Relative humidity: the daily average relative humidity is not more than 95%, and the monthly average relative humidity is not more than 90%.
  • Seismic intensity: not exceeding 8 degrees.
  • Places without fire, explosion hazards, serious pollution, chemical corrosion, and severe vibration.

Performance Parameter

Item Unit Parameters
Rated Voltage kV 12
Rated Frequency Hz 50
Rated Current of Main Busbar / Max Rated Current of Fuse A 630 / 125
Rated Short-Time Withstand Current of Main Circuit and Earth Circuit kA / s 20 / 3
Rated Peak Withstand Current of Main Circuit and Earth Circuit kA 50
Rated Short-Circuit Making Current of Main Circuit and Earth Circuit kA 50
The Opening Times of the Load Switch with Full Capacity times 100
Fuse Breaking Current kA 40
Rated Closed Loop Breaking Current A 630
Rated Transfer Current A 1600
Mechanical Life times 2000
1min Power Frequency Withstand Voltage (Peak Value) Between Phases, Phase and Earth / Phase and Isolation Fracture kV 42 / 48
Lightning Impulse Withstand Voltage (Peak Value) Between Phases, Phase and Earth / Phase and Isolation Fracture kV 75 / 85
Secondary Loop 1min Power Frequency Withstand Voltage kV 2
Protection Level IP3X

Связанные модели в категории Средневольтные КРУ