20kV Dry-Type Transformer
20kV cast-resin dry-type transformer for projects requiring low maintenance and indoor safety.
Ключевые характеристики
Номинальная мощность
50-2500 kVA
Класс напряжения
20kV / 22kV / 24kV / 0.4kV / 0.415kV / 0.433kV
Изоляция
Cast Resin
Монтаж
Indoor
Product Overview
This series of dry-type transformers with fillers and thin insulation uses epoxy resin encapsulated coils, making the transformers flame-retardant, fireproof, explosion-proof, maintenance-free, pollution-free, and compact enough for direct installation in the load center.
Meanwhile, the scientific and reasonable design and pouring process give the product lower partial discharge, lower noise, and stronger heat dissipation capacity. Under forced air cooling conditions, it can operate continuously at 140% of the rated load for a long time and can be equipped with an intelligent temperature controller for centralized monitoring and control.
The foil-type coil can solve problems such as high short-circuit stress in low-voltage and large-current windings, unbalanced ampere-turns, poor heat dissipation effect, large winding helix angle, and unstable manual welding quality.
At the same time, the winding ends adopt resin sealing, curing, moisture-proof, and anti-fouling measures, and the copper busbars are automatically welded by argon arc welding.
Applicable Standards
- GB 1094-2013 Power Transformer
- GB/T 2900.95 Electrical Terms: Transformers, Voltage Regulators and Reactors
- GB/T 10228 Technical Parameters and Requirements of Dry Type Power Transformers
- GB 20052-2020 Power Transformer Energy Efficiency Limit Value and Energy Efficiency Grade
- IEC 60076 Power Transformer
Normal Service Conditions
- Installation altitude below 1000 meters.
- Highest ambient temperature: +40 degrees Celsius.
- Highest daily average temperature: +20 degrees Celsius.
- Lowest outdoor temperature: -20 degrees Celsius.
Performance Parameters
SCB10 Series Technical Parameter Table
| Rated Capacity (kVA) | Voltage Group | Vector Group | Impedance Voltage (%) | No-Load Loss (W) | Load Loss F/120C (W) | Load Loss H/145C (W) | No-Load Current (%) | Dimensions (mm) | Weight (kg) | ||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| HV (kV) | Tap Range | LV (kV) | L | W | H | ||||||||
| 50 |
20 22 24 |
±2x2.5% ±5% |
0.4 0.415 0.433 |
Yyn0 Dyn11 | 6.0 | 340 | 1230 | 1310 | 2.0 | 750 | 600 | 800 | 520 |
| 100 | 540 | 1990 | 2130 | 1.8 | 950 | 700 | 840 | 750 | |||||
| 160 | 670 | 2470 | 2640 | 1.5 | 1000 | 950 | 760 | 870 | |||||
| 200 | 730 | 2940 | 3140 | 1.5 | 1100 | 950 | 820 | 900 | |||||
| 250 | 840 | 3420 | 3660 | 1.3 | 1230 | 950 | 1450 | 1250 | |||||
| 315 | 970 | 4080 | 4360 | 1.3 | 1260 | 1000 | 1500 | 1420 | |||||
| 400 | 1150 | 4840 | 5180 | 1.1 | 1340 | 1050 | 1650 | 1820 | |||||
| 500 | 1350 | 5790 | 6190 | 1.1 | 1400 | 1150 | 1650 | 2180 | |||||
| 630 | 1530 | 6840 | 7320 | 1.0 | 1410 | 1150 | 1650 | 2380 | |||||
| 800 | 1750 | 8260 | 8840 | 1.0 | 1470 | 1250 | 1750 | 2640 | |||||
| 1000 | 2070 | 9780 | 10400 | 0.85 | 1530 | 1300 | 1750 | 3010 | |||||
| 1250 | 2380 | 11500 | 12300 | 0.85 | 1580 | 1300 | 1850 | 3650 | |||||
| 1600 | 2750 | 13800 | 14800 | 0.85 | 1680 | 1400 | 1850 | 4450 | |||||
| 2000 | 3240 | 16300 | 17500 | 0.7 | 1770 | 1450 | 2050 | 5630 | |||||
| 2500 | 3870 | 19300 | 20700 | 0.7 | 1850 | 1450 | 2150 | 6610 | |||||