35kV Oil-Immersed Transformer

  • Home
  • 35kV Oil-Immersed Transformer
35kV Oil-Immersed Transformer

35kV Oil-Immersed Transformer

Energy-efficient 35kV-class oil-immersed transformer for commercial distribution, residential communities, rural grids, heavy industrial loads, and township substations.

Quick Specifications

Power Rating

30-31500 kVA

Voltage Class

33kV / 35kV / 38.5kV, 0.4-11kV secondaries

Frequency

50/60 Hz

Application

Commercial / Residential / Rural Grid / Heavy Industry / Township Substations

Product Overview

This series of oil-immersed transformers breaks through the traditional planar structure and adopts a three-phase symmetrical three-dimensional structure.

The magnetic circuits of the three-phase iron cores are completely symmetrical, which greatly reduces magnetic resistance and significantly lowers exciting current and no-load loss.

It is an energy-efficient transformer that uses traditional materials while achieving lower operating noise and a more compact overall structure.

The design delivers strong performance in energy conservation, consumption reduction, material saving, and environmental protection.

Application Scenarios

  • Commercial power distribution
  • Residential community power supply
  • Rural power grid distribution
  • Heavy industrial power supply
  • Township small-scale substations

Applicable Standards

  • GB 1094-2013 Power Transformer
  • GB/T 6451-2015 Technical Parameters and Requirements for Oil-Immersed Power Transformers
  • IEC 60076 Power Transformers

Normal Service Conditions

  • Installation altitude below 1000 meters.
  • Highest ambient temperature: +40 degrees Celsius.
  • Highest daily average temperature: +20 degrees Celsius.
  • Lowest outdoor temperature: -25 degrees Celsius.

Performance Parameters

The tables below show representative 35kV-class technical data for low-voltage distribution service and medium-voltage substation applications.

35kV Series Technical Parameter Table (30-2500 kVA)

Rated Capacity (kVA) Voltage Group (HV / LV) Vector Group No-Load Loss (W) Load Loss (W) No-Load Current (%) Impedance Voltage (%) Boundary Dimensions (L x W x H, mm) Weight (kg)
30 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 100 690 / 660 2.1 5.5 670 x 310 x 615 346
50 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 130 1010 / 960 2.0 5.5 700 x 325 x 630 417
80 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 180 1440 / 1370 1.8 5.5 755 x 355 x 690 556
100 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 200 1730 / 1650 1.6 5.5 785 x 360 x 685 619
125 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 240 2080 / 1980 1.5 5.5 805 x 370 x 720 703
160 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 290 2540 / 2420 1.4 5.5 850 x 385 x 735 794
200 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 340 3000 / 2860 1.3 5.5 865 x 405 x 805 935
250 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 400 3520 / 3350 1.2 5.5 905 x 415 x 935 1086
315 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 480 4210 / 4010 1.1 5.5 925 x 440 x 915 1226
400 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 570 4970 / 4730 1.0 5.5 970 x 465 x 960 1468
500 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 680 5940 / 5660 1.0 5.5 1035 x 500 x 1010 1758
630 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 810 6820 0.9 6.0 1110 x 525 x 1075 2074
800 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 980 8250 0.8 6.0 1190 x 580 x 1155 2840
1000 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 1150 11330 0.7 6.0 1205 x 560 x 1195 2842
1250 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 1380 13200 0.7 6.0 1185 x 590 x 1205 3168
1600 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 1660 15950 0.6 6.0 1225 x 565 x 1345 3800
2000 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 1950 19140 0.6 6.0 1310 x 615 x 1435 4633
2500 33 / 35 / 38.5 kV / 0.4 kV Dyn11 / Yyn0 2340 22220 0.5 6.0 1390 x 660 x 1510 5329

35kV Series Technical Parameter Table (630-31500 kVA)

Rated Capacity (kVA) Voltage Group (HV / LV) Vector Group No-Load Loss (W) Load Loss (W) No-Load Current (%) Impedance Voltage (%) Boundary Dimensions (L x W x H, mm) Weight (kg)
630 33 / 35 / 38.5 kV / 3.15 / 6.3 / 10.5 kV Yd11 830 7860 0.65 6.5 2300 x 1100 x 2000 2610
800 33 / 35 / 38.5 kV / 3.15 / 6.3 / 10.5 kV Yd11 980 9400 0.65 6.5 2390 x 1130 x 2070 3310
1000 33 / 35 / 38.5 kV / 3.15 / 6.3 / 10.5 kV Yd11 1150 11500 0.65 6.5 2420 x 1200 x 2110 3580
1250 33 / 35 / 38.5 kV / 3.15 / 6.3 / 10.5 kV Yd11 1400 13900 0.55 6.5 2500 x 1270 x 2130 3990
1600 33 / 35 / 38.5 kV / 3.15 / 6.3 / 10.5 kV Yd11 1690 16600 0.45 6.5 2510 x 1290 x 2340 4740
2000 33 / 35 / 38.5 kV / 3.15 / 6.3 / 10.5 kV Yd11 2170 18300 0.45 6.5 2420 x 2070 x 2390 5120
2500 33 / 35 / 38.5 kV / 3.15 / 6.3 / 10.5 kV Yd11 2560 19600 0.45 6.5 2520 x 2210 x 2470 5880
3150 33 / 35 / 38.5 kV / 3.15 / 6.3 / 10.5 kV Yd11 3040 23000 0.45 7.0 2630 x 2280 x 2510 7770
4000 33 / 35 / 38.5 kV / 3.15 / 6.3 / 10.5 kV Yd11 3610 27300 0.45 7.0 2720 x 2430 x 2570 8750
5000 33 / 35 / 38.5 kV / 3.15 / 6.3 / 10.5 kV Yd11 4320 31300 0.45 7.0 2870 x 2470 x 2750 9930
6300 33 / 35 / 38.5 kV / 3.15 / 6.3 / 10.5 kV Yd11 5250 35000 0.45 7.0 3100 x 2580 x 2950 12760
8000 33 / 35 / 38.5 kV / 3.15 / 3.3 / 6.3 / 6.6 / 10.5 / 11 kV YNd11 7200 38400 0.35 8.0 3250 x 2680 x 3150 14500
10000 33 / 35 / 38.5 kV / 3.15 / 3.3 / 6.3 / 6.6 / 10.5 / 11 kV YNd11 8700 45300 0.35 8.0 3320 x 2720 x 3230 16900
12500 33 / 35 / 38.5 kV / 3.15 / 3.3 / 6.3 / 6.6 / 10.5 / 11 kV YNd11 10000 53800 0.30 8.0 3410 x 2950 x 3410 19980
16000 33 / 35 / 38.5 kV / 3.15 / 3.3 / 6.3 / 6.6 / 10.5 / 11 kV YNd11 12100 65800 0.30 8.0 3600 x 3220 x 3630 24200
20000 33 / 35 / 38.5 kV / 3.15 / 3.3 / 6.3 / 6.6 / 10.5 / 11 kV YNd11 14400 79500 0.30 8.0 3810 x 3640 x 4040 31200
25000 33 / 35 / 38.5 kV / 3.15 / 3.3 / 6.3 / 6.6 / 10.5 / 11 kV YNd11 17000 94000 0.25 10.0 4180 x 4170 x 4260 36100
31500 33 / 35 / 38.5 kV / 3.15 / 3.3 / 6.3 / 6.6 / 10.5 / 11 kV YNd11 20200 112000 0.25 10.0 4820 x 4630 x 4440 42600

FAQ

Of course. This product covers the voltage class commonly used in Asian markets. Its highest voltage class is 40.5 kV, so 33 kV is fully within the supported range. We can absolutely manufacture a 33 kV / 0.433 kV version for your project.
Yes. We can customize the HV/LV voltage combination, vector group, tapping range, impedance voltage, terminal arrangement, protective accessories, and coating specification to match utility, EPC, and industrial project requirements.
It is widely used in commercial distribution, residential communities, rural power networks, heavy industrial facilities, and township substations that require reliable medium-voltage power transformation.
We can provide datasheets, outline drawings, nameplate details, routine test reports, certificate files, and commercial quotations to support engineering evaluation and purchasing.

Back to Oil-Immersed Transformers or contact us for datasheets and quotations.