Single Phase Oil Immersed Transformer

  • Home
  • Single Phase Oil Immersed Transformer
Single Phase Oil Immersed Transformer

Single Phase Oil Immersed Transformer

Single-phase oil-immersed transformer designed for electrical circuit wiring and equipment matching, delivering stable output, efficient operation, and reliable long-term performance.

Quick Specifications

Power Rating

30-2500 kVA

Product Type

Single-Phase Oil-Immersed

Core Options

Electrical Steel / Amorphous Alloy

Application

Circuit Wiring / Equipment Matching

Product Overview

The structural design of the single-phase oil-immersed transformer with second-level energy efficiency is advanced, and high-temperature insulation materials that are resistant to both sound and visual influence are adopted. It has the characteristics of good no-load energy consumption, safety, and reliability, ensuring stable power output.

It is mainly used for the wiring of electrical circuits, electrical equipment, and electromechanical equipment, providing stable power output quality for the power matching of various electrical and mechanical equipment.

It has a high insulation class and stable, reliable performance. In practical applications, it can provide continuous and stable high-quality voltage transformation services.

It has high working efficiency and can provide efficient power output to ensure the safe operation of the power supply.

It has good heat dissipation performance and excellent performance reliability during long-term operation.

Applicable Standards

  • GB 1094-2013 Power Transformer
  • GB/T 2900.95 Electrical Terms: Transformers, Voltage Regulators and Reactors
  • GB/T 10228 Technical Parameters and Requirements of Dry Type Power Transformers
  • GB 20052-2020 Power Transformer Energy Efficiency Limit Value and Energy Efficiency Grade
  • IEC 60076 Power Transformer

Normal Service Conditions

  • Installation altitude below 1000 meters.
  • Highest ambient temperature: +40 degrees Celsius.
  • Highest daily average temperature: +20 degrees Celsius.
  • Lowest outdoor temperature: -20 degrees Celsius.

Performance Parameters

Single Phase Oil-Immersed Transformer Technical Parameter Table

Rated Capacity (kVA) Electrical Steel Belt Amorphous Alloy Impedance Voltage (%)
No-Load Loss (W) Load Loss (W) No-Load Loss (W) Load Loss (W)
B (100C) F (120C) H (145C) B (100C) F (120C) H (145C)
30 105 605 640 685 50 605 640 685 4.0
50 155 845 900 965 60 845 900 965 4.0
80 210 1160 1240 1330 85 1160 1240 1330 4.0
100 230 1330 1415 1520 90 1330 1415 1520 4.0
125 270 1565 1665 1780 105 1565 1665 1780 4.0
160 310 1800 1915 2050 120 1800 1915 2050 4.0
200 360 2135 2275 2440 140 2135 2275 2440 4.0
250 415 2330 2485 2665 160 2330 2485 2665 4.0
315 510 2945 3125 3355 195 2945 3125 3355 4.0
400 570 3375 3590 3850 215 3375 3590 3850 4.0
500 670 4130 4390 4705 250 4130 4390 4705 4.0
630 775 4975 5290 5660 295 4975 5290 5660 4.0
630 750 5050 5365 5760 290 5050 5365 5760 6.0
800 875 5895 6265 6715 335 5895 6265 6715 6.0
1000 1020 6885 7315 7885 385 6885 7315 7885 6.0
1250 1205 8190 8720 9335 455 8190 8720 9335 6.0
1600 1415 9945 10555 11320 530 9945 10555 11320 6.0
2000 1760 12240 13005 14005 700 12240 13005 14005 6.0
2500 2080 14535 15445 16605 840 14535 15445 16605 6.0

Back to Oil-Immersed Transformers or contact us for datasheets and quotations.